How to Read an MCB Marking: Rated Current, Curve, Voltage and kA

October 4, 2026 · 3 min read
Short answer

An MCB marking such as “C32 · 230/400 V~ · 6000” tells you the trip curve (C), the rated current (32 A), the rated voltage and — in the boxed number — the rated short-circuit capacity (6000 A = 6 kA). A small digit under that box is the energy-limiting class. Check each marking against the datasheet and the certificate for the ordering code.

Key facts

  • The letter before the number is the trip curve; the number is the rated current In in amperes.
  • The boxed number is the rated short-circuit capacity in amperes (6000 = 6 kA, 10000 = 10 kA).
  • Rated current is defined at a reference ambient temperature (30 °C in IEC 60898-1) — hot enclosures need derating.

Marking decoder

Marking Meaning Why it matters
C32 Trip curve C, rated current 32 A Curve decides tolerance to inrush; In must suit the cable
230/400 V~ Rated voltage (single-phase / three-phase), AC Must match the system voltage
50 Hz Rated frequency MCBs are frequency-insensitive; contactor coils are not
6000 (in a box) Rated short-circuit capacity, 6 kA Must be at least the fault level at the board
3 (below the box) Energy-limiting class 3 Higher class limits let-through energy better
IEC/EN 60898-1 Standard the breaker is certified to Household-type installations; see 60898-1 vs 60947-2
CE / CB marks Conformity and test-report scheme marks Not a substitute for a destination scheme such as EAC or SONCAP
Laser batch, QR code Traceability to the factory lot The first thing to check against paperwork

Example: NB1-63 and NB1-63H

The CHINT NB1-63 carries a 6 kA rating; the NB1-63H is the 10 kA version for feeders close to a transformer. Their housings look alike, so the boxed number is the quickest visible difference — and the first thing a counterfeit gets wrong.

How a wrong marking shows up

  • The boxed value differs from the datasheet for that ordering code.
  • Print quality or fonts differ between units in the same carton.
  • No batch code, or a batch that does not match the paperwork.
  • A QR code that does not return factory data when scanned.

Run the physical checks in our genuine-product checklist before you accept a delivery.

Frequently asked questions

What does the number in the box on an MCB mean?

It is the rated short-circuit capacity in amperes. 6000 means 6 kA; 10000 means 10 kA.

Is a C-curve MCB better than a B-curve?

Neither is better in general. C tolerates higher inrush than B, which suits mixed loads; B suits long cable runs and resistive circuits. See MCB trip curves.

Can I use a 6 kA MCB where 10 kA is required?

No. The breaking capacity must be at least the prospective fault current. See 6 kA vs 10 kA.

Get a real quotation, not a brochure.

Send model or photo · quantity · destination country · grid (V / Hz / 1φ or 3φ) · required certificate. You get unit price, packing data (carton / pcs / GW / CBM), lead time and the certificate list in one message, within 24 hours.

Reviewed by the HAZAM technical team, October 2026. CHINT, DELIXI and TENGEN are trademarks of their respective owners. HAZAM is a first-tier authorised distributor of CHINT products; the authorisation certificate is available on request from our sales manager. Ratings and designations refer to published manufacturer documentation; the certificate for your exact ordering code governs.

Need this checked against your order?

Send the model, quantity and destination — we reply with the correct code, certificate position and price within 24 hours.

WhatsApp E-mail