The DC side has no zero crossing. Voltage, poles and trip curve decide whether the breaker protects the string or becomes the weak point.

1000/1500 VDC ratings
2P/4Ppole options
32–63 Atypical string range
IEC 60947-2breaker standard

1000 V or 1500 V

The breaker voltage must be at least the maximum string voltage at the lowest expected temperature — not the nominal system voltage.

SystemBreaker ratingTypical useWatch out for
1000 V DC1000 V DCResidential and small commercial stringsCold-weather Voc can exceed the nominal voltage
1500 V DC1500 V DCUtility-scale and large commercial stringsSeries rating and enclosure clearance
1000 V DC1000 V DCBattery DC side (lower voltage)Different fault current from a PV string

2P or 4P

2P

One positive and one negative pole in a single device. Common for smaller strings and tight enclosures.

4P

Two strings or a higher current path in one device. Confirm whether the poles are internally linked and how the series rating applies.

Isolator

A visible break for maintenance. It does not replace overcurrent protection. Some projects require both an MCB and an isolator.

Trip curve

PV strings have a limited fault current. The magnetic trip must still respond; the thermal trip must not nuisance-trip on a hot roof.

Typical DC breaker range

Model typePolesCurrentVoltageStandard
DC MCB2P32 A1000 V DCIEC 60947-2
DC MCB4P63 A1000 V DCIEC 60947-2
DC MCB2P32 A1500 V DCIEC 60947-2
DC MCB4P63 A1500 V DCIEC 60947-2
DC isolator3P/4P32 A1000 V DCIEC 60947-3

Typical range for quotation. Final ratings, breaking capacity and certificate coverage are confirmed per model.

Installation checks

  • Confirm the maximum Voc at the lowest ambient temperature, then add the temperature coefficient margin.
  • Check the polarity: DC breakers are not all symmetrical. Follow the manufacturer’s line/load marking.
  • Use an enclosure rated for the location; DC arcs need adequate clearance and a DC-rated device.
  • Torque the terminals to the datasheet value and re-check after the first thermal cycle.
  • Label the string and the breaker; a combined array is hard to isolate without a map.

DC breaker questions

Can I use an AC MCB on the DC side?

No. AC breakers rely on a zero crossing to extinguish the arc. A DC breaker needs a DC-rated arc chamber and a DC breaking capacity.

What voltage should I choose?

At least the maximum string voltage at the lowest expected temperature. A 1000 V system can exceed 1000 V Voc on a cold morning; leave margin.

2P or 4P: which one?

2P for a single string or a compact enclosure; 4P for two strings or a higher current path. Confirm whether the poles are linked and how the series rating is declared.

Do I need a DC isolator as well as an MCB?

Many installations do. The MCB protects against overload and short circuit; the isolator provides a visible break for maintenance. Check the local installation code.

What breaking capacity do I need?

It depends on the available fault current at the array. A PV string has a limited fault current, but the combiner and battery side can be different. The designer should confirm.

Can the breaker be used for battery DC?

Only if the rating and the certificate cover the battery voltage and the available fault current. A PV string breaker is not automatically a battery breaker.

Do you provide the IEC 60947-2 certificate?

Yes, for the models where the factory holds it. We send the certificate and the model list so you can check the exact rating.

What is the minimum order?

One carton for most models. Mixed cartons are possible; the packing list shows the exact quantity.

Send your DC breaker requirement

Tell us the system voltage, string current, pole count and quantity. We reply with the model and certificate.

Request a quote →
Telegram E-mail
RUAR