Surge Protective Devices: Type 1, Type 2 and Type 3 Explained

October 3, 2026 · 3 min read
Short answer

Type 1 SPDs handle partial lightning current (10/350 µs test waveform) at the service entrance; Type 2 SPDs handle induced and switching surges (8/20 µs) at distribution boards; Type 3 SPDs protect sensitive equipment close to the load. Most buildings need Type 2 at the main board; add Type 1, or a combined Type 1+2 such as the NU6-I+II, where an external lightning protection system or overhead lines expose the building.

Key facts

  • SPD classes are defined in IEC 61643-11 (EN 61643-11 uses “Type 1 / 2 / 3”).
  • Uc is the maximum continuous operating voltage; Up is the voltage protection level the SPD lets through. A low Up protects better; Uc must suit the system.
  • An SPD does not replace an RCD or MCB — it works alongside them, usually with a backup protective device specified by the SPD datasheet.

Type 1, 2 and 3 compared

Type 1 Type 2 Type 3
Test waveform 10/350 µs (lightning current, Iimp) 8/20 µs (In / Imax) Combination wave (Uoc)
Protects against Direct and partial lightning current Induced surges and switching surges Residual surges at the equipment
Typical location Service entrance of buildings with an external lightning protection system or overhead supply Main and sub-distribution boards At or next to sensitive loads
CHINT example NU6-I+II (combined Type 1+2) NU6-II —

Choosing Uc for your earthing system

Uc must be chosen against the earthing system and the measured supply voltage. A Uc of 275 V is common on TN systems at 230/400 V; some earthing arrangements, such as IT, need a higher Uc (for example 440 V). On a legacy 127 V system the figures change again — size the SPD against the real system voltage, not the nameplate of the building. See our Saudi Arabia guide for the 127 V / 60 Hz case.

Selection checklist

  1. Earthing system (TN-S, TN-C-S, TT, IT) and nominal voltage.
  2. Is the building exposed — lightning rod, overhead line, tall structure? If yes, Type 1 or Type 1+2 at the entrance.
  3. Distance between SPD and protected equipment: add a Type 2 or Type 3 further downstream where the cable run is long.
  4. The backup fuse or MCB the datasheet requires, and its rating.
  5. Single-phase or three-phase, number of protected poles (for example 3P+N).

Browse the SPD, ATSE and isolator range or send your earthing system and board details for a quotation.

Frequently asked questions

Do I need an SPD if there is no lightning rod?

Often yes. Overhead supply lines and switching events cause surges even without direct lightning, which is what Type 2 devices address.

What does Type 1+2 mean?

A combined device tested to both the Type 1 (10/350 µs) and Type 2 (8/20 µs) requirements, so one unit covers service-entrance duty and board-level protection.

Is an SPD the same as a surge-protected power strip?

No. A board-level SPD is installed in the distribution board and protects the whole installation; a power strip is a Type 3 style device for individual equipment.

Get a real quotation, not a brochure.

Send model or photo · quantity · destination country · grid (V / Hz / 1φ or 3φ) · required certificate. You get unit price, packing data (carton / pcs / GW / CBM), lead time and the certificate list in one message, within 24 hours.

Reviewed by the HAZAM technical team, October 2026. CHINT, DELIXI and TENGEN are trademarks of their respective owners. HAZAM is a first-tier authorised distributor of CHINT products; the authorisation certificate is available on request from our sales manager. Ratings and designations refer to published manufacturer documentation; the certificate for your exact ordering code governs.

Need this checked against your order?

Send the model, quantity and destination — we reply with the correct code, certificate position and price within 24 hours.

WhatsApp E-mail